67
• C-Bus
®
BACnet Gateway is a hardware interface
• Allows exchange of information between C-Bus
®
and a
Building Management System supporting the BACnet
protocol
• One full C-Bus
®
lighting application supported
• BACnet values supported: analogue read, analogue write
and binary read
• Supplied pre-confi gured
• Supplied with an enclosure, C-Bus
®
PC Interface and
BACnet module power supply
C-Bus
®
BACnet Gateway
5000BACNET
C-Bus
®
BACnet
Gateway
• C-Bus
®
to DALI Gateway,
DIN rail mounted
• 4M DIN modules wide
• Dimensions 72mm x 85mm x 65mm
• Supports DALI lamp and ballast failure information to be
available on the C-Bus
®
network
• Capable of controlling up to two DALI networks
• The unit supports DALI group addresses, short addresses
and scenes the DALI global (broadcast) address
• A remote switch input is included to turn all DALI output
channels to the ON or OFF states, irrespective of the
current state of the C-Bus
®
, including no C-Bus
®
• Incorporates the C-Bus
®
clock signal and a network burden
• Up to 50 DALI Gateways can be connected to a single
C-Bus network
• Units Draw 32mA from a C-Bus
®
network
C-Bus
®
DALI Gateway
5502DAL
C-Bus
®
DALI Gateway
• C-Bus to DALI Gateway,
DIN rail mounted
• 4M DIN modules wide
• Dimensions 72mm x 85mm x 65mm
• Supports DALI lamp and ballast failure information to be
available on the C-Bus
®
network
• Capable of controlling up to two DALI networks
• The unit supports DALI group addresses, short addresses
and scenes the DALI global (broadcast) address
• A remote switch input is included to turn all DALI output
channels to the ON or OFF states, irrespective of the
current state of the C-Bus, including no C-Bus
®
• Incorporates the C-Bus
®
clock signal and a network burden
• Up to 50 DALI Gateways can be connected to a single
C-Bus network
• Units Draw 32mA from a C-Bus
®
network
• Supplied with two DIN DALI power supply modules
5502DAL2PS
C-Bus
®
DALI Gateway plus
two DALI power supplies