C-Bus™ Basic Programming 1250SM0904R10/09
C-Bus™ Products Training Course 10/2009
88 © 2009 Schneider Electric. All Rights Reserved.
Serial Number Readdress
A much quicker way to readdress the network to match the database, is to
use the Serial Number Readdress function. This can only be used if you:
manually type the serial number into each unit in the database, or
use the C-Bus Barcode Scanner to add C-Bus units to the Database.
Once you have a database fully populated with C-Bus units with serial
numbers, you may readdress the entire network in a much quicker process,
as listed below:
1) Scan the C-Bus network.
2) Navigate to the Units On Network toolbar in the Programming window,
and click on the small arrow to the right hand side of the Readdress
button. This will display more buttons related to readdressing C-Bus
units. Click on the Serial Number Readdress button and the form
below will appear.
Figure 66 - Readressing C-Bus units to match by serial number
3) Click on the Readdress button. Once completed an information form
will pop up to indicate that the readdressing process is complete.
Press the OK button.
4) Press the Close button to shutdown the Serial Number Readdress
form.
5) You will now find that the unit addresses for all C-Bus units are
identical in the network and database.