1250SM0904R10/09 C-Bus™ Basic Programming
10/2009 C-Bus™ Products Training Course
© 2009 Schneider Electric. All Rights Reserved. 35
C-Bus Current
Each C-Bus network can only have a maximum of 2 A of current being
provided and drawn. Exceeding the 2 A limit could:
damage the C-Bus cable in a short circuit condition
cause unexpected behaviour.
The table below lists the different C-Bus power supplies and the amount of
current that they provide to the
C-Bus network.
Type Of C-Bus Power Supply Output Current
DIN Rail Stand Alone 350 mA
DIN Rail Onboard 200 mA
Old Pro Series Dimmer Onboard 60 mA
Matrix Switcher 330 mA
Table 15 - C-Bus Power Supply output currents
NOTE: The full 2 Amps of C-Bus current may not be required for the C-Bus
network to operate. Ensure that the current drawn by all C-Bus units does
not exceed the total current provided by all C-Bus Power Supplies.
The following example explains how to calculate the required C-Bus current
for stable C-Bus operation. To calculate the total amount of current needed
to provide power to the network, simply:
1) Add up the current consumption of all of the C-Bus input units and
System Support Devices.
2) Ensure that the C-Bus Power Supplies that are being used provide
more current than the current being used by all of the input units and
System Support Devices.
Input Units and System Support Device Current Calculation
Unit Type Quantity Current Drawn Total Current
USB PC Interface 1 32 mA 32 mA
4 Button Switch (Standard) 12 18 mA 216 mA
6 Button Switch (Saturn) 5 22 mA 110 mA
8 Button Switch (Neo) 3 22 mA 66 mA
Multi Sensor 5 18 mA 90 mA
Colour Touch Screen 2 22 mA 44 mA
Total Current Draw: 558 mA