2C. Advanced Programming
Function Action
Idle No action
Store 1 This stores the current level in internal the Recall 1 memory location (Blocks
tab). When the Recall 1 function is used, the group level reverts to this state.
The level is stored in non-volatile memory. No transmission is made over the
C-Bus
®
Network.
Downcycle The output level is ramped down to minimum. If the output is already at
minimum, it ramps up to maximum.The Downcycle function should be used
in conjunction with the End Ramp function to ensure that ramping ends
at the desired level. The direction of output ramping changes with each
successive Downcycle / End Ramp operation. This allows a single button
to act as an up/down light dimmer. The Off Key function can be used to
terminate ramping if required. A RAMP TO LEVEL message is transmitted
over the C-Bus Network.
Memory Toggle If the output is on, the Memory Toggle function stores the current level in
the Recall 2 memory location (Blocks tab) and switches the output off. If the
output is off, the function sets the output to the last level stored in the Recall
2 memory location (the previous brightness level). An OFF or RAMP TO
LEVEL message is transmitted over the C-Bus Network.
Down Key This function is similar to Downcycle except that it can only ramp the output
level downwards. The output will be ramped to the minimum level unless
either the End Ramp or Off Key function terminates the process early. The
ramp rate for the Down Key function is set by the 'Ramp 1' parameter
(Global tab). The Down Key function has no effect if the current output is in
the off state. A RAMP TO LEVEL message is transmitted over the C-Bus
Network.
Up Key The output level increases to the maximum level, unless either the End
Ramp or Off Key function ends the process early. The ramp rate for the Up
Key function is set by the 'Ramp 1' parameter (Global tab). If the current
level is already at a maximum, no action will occur. A RAMP TO LEVEL
message is transmitted over the C-Bus Network.
Recall 1 The output level is set to the level stored in the Recall 1 memory location
(Blocks tab). A RAMP TO LEVEL message is transmitted over the C-Bus
Network.
Recall 2 The output level is set to the level stored in the Recall 2 memory location
(Blocks tab). A RAMP TO LEVEL message is transmitted over the C-Bus
Network.
Retrigger Timer The retrigger timer command starts the internal timer only if the output is
currently on (at any level). If the output is already on, the timer is restarted.
A RAMP TO LEVEL message is transmitted over the C-Bus Network.
Start The internal timer is started without affecting the output level (if the timer
value is greater than zero).An ON message may be transmitted over the
C-Bus Network.