Clipsal C-Bus User Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 15
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
©2008 Schneider Electric. All Rights Reserved.
Toggle/Local Override/Channel Control Buttons
On output units (e.g., DIN-rail Dimmers and Relays), these buttons operate a unit’s
output channels and LEDs, as long as the unit is connected to line voltage. Use
them to verify that the power lines are installed correctly and that each channel
switches the correct load(s). These buttons are multi-functional.
Override Button Functions
The Toggle’s Status Indicator LED shows the status (ON or OFF) of each channel on
that output unit.
Light ON/lit, the channel is ON; light OFF/unlit, the channel is OFF.1.
A press on a Toggle/Local Override/Channel Control button manually overrides 2.
the current state of that channel.
Local Override/Channel Control buttons can be used to start Learn Mode and 3.
configure a unit.
Override Button Operations
When one or more channels or units are in Local Override mode, different button
presses have different effects.
Short press: “Toggles” that channel/unit, e.g., from OFF to ON.•
Double press: Returns control of that channel/unit to the C-Bus network.•
Long press: All channels or units in Local Override mode are returned to control •
by the C-Bus network.
VERIFYING NETWORK POWER
The amount of current required for a C-Bus network depends on the current drawn
by its C-Bus units. Typical C-Bus units draw 18–40 mA, and many networks require
less than 2 A. See a unit’s illustration or installation bulletin to determine its current
requirements. The steps below summarize how to calculate a network’s power
requirements and verify that only 2 A will be supplied to the network. (The C-Bus
Toolkit software will also calculate this for you.)
STEP 1: Add up the current consumed by all the input, system support, and output
units that draw power from the C-Bus network. Remember that the combined
current consumed by all these units must not exceed 2 A.
Unit Type No.
Units
Current Draw Total Current Draw
USB PC Interface 1 32 mA 32 mA
4-Button Decorator Keypad 12 22 mA 264 mA
6-Button Saturn Keypad 5 22 mA 110 mA
8-Button Neo Keypad 3 22 mA 66 mA
Light-Level Sensor 5 18 mA 90 mA
Color Touch Screen 2 22 mA 44 mA
Total Drawn 606 mA
Page view 12